Description
Merus Uninterrupted Power Quality (UPQ) is an innovative concept, combining the functionalities of a UPS and an active harmonic filter into a single robust solution. UPQ protects mission critical processes from supply interruptions and voltage sags while maintaining supply voltage quality by compensating harmonic currents and the reactive power fluctuations of non-linear loads.
Merus UPQ has two operation modes. In secured supply conditions, it operates in power quality mode, performing active filtering of harmonic distortions as well as load balancing and flicker mitigation. When it detects a voltage sag or power outage in the supply network, it shifts to power protection mode to protect against critical loads. Merus UPQ is available for two ranges of nominal voltage: 200÷400V, sau 225÷750V. Merus Power can supply a complete turnkey solution.
Technical data
- Power system: 3 Phases + Neutral (4 wire)
- Nominal system frequency: 50Hz or 60 Hz
- Load protection time (in Protection mode): 3s (Other protection time capacities are available on request)
- Energy storage media: Ultra Capacitors (Other energy storage meida available on request)
- Transition time: < 1.8 ms
- Operation modes (in Power quality mode): All harmonics / All harmonics but not fundamental / Selective harmonics
- DOL (Direct On Line) Motor Starting: Enabled and supported
- Human Machine Interface (HMI): 7" touch screen display
- Monitoring: on-site and remote
- Reporting: reports data of power quality events from last 30 days
- Communication: Ethernet / RS485, ModBus TCP/IP